Section 6
Electrical System
Part No. 80-1214-3
6-51
4. Disconnect water level probe from control board. Install jumper from control board “water level” terminal to
ground.
5. Move the toggle switch from ICE to OFF to ICE position. Wait 45 seconds, then monitor the Water Level Probe
light.
WATER LEVEL PROBE CLOSED OR SHORTED
1. Disconnect the water level probe from the control board.
2. Move the toggle switch to the ICE position, wait 45 seconds and then monitor the Water Level Probe light.
Step 5 Jumper “water level” terminal to ground
Water Level light is:
Compressor
Cause
On
Energizes
Replace water level probe wiring.
(Verify defective component – ohm wire from
connector to connector.)
Off
Remains de-energized
Replace control board.
Step 2 Disconnect water level probe from control board “water level” terminal
Water Level light is:
Compressor
Cause
Off
Remains de-energized
Clean water level probe.
On
Energizes
Replace control board.
SV2035
WATER LEVEL
PROBE LIGHT
DISCONNECT
WATER LEVEL PROBE.
JUMPER FROM
CONTROL BOARD
“WATER LEVEL” TO
GROUND
SV2036
DISCONNECT
WATER LEVEL PROBE.
WATER LEVEL
PROBE LIGHT
Revised 8/2003
Содержание QC0700
Страница 8: ...Table of Contents continued 6 Part No 80 1214 3 Revised 8 2003 ...
Страница 12: ...General Information Section 1 1 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 30: ...Installation Instructions Section 2 2 18 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 52: ...Ice Machine Sequence of Operation Section 4 4 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 122: ...Electrical System Section 6 6 60 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 144: ...Refrigeration System Section 7 7 22 Part No 80 1214 3 Using Pinch Off Tool SV1406 Revised 8 2003 ...
Страница 147: ...Revised 8 2003 ...
Страница 150: ...Refrigeration System Section 7 7 26 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...