Electrical System
Section 6
6-56
Part No. 80-1214-3
FAN CYCLE CONTROL
Function
Cycles the condenser fan motor on and off to maintain
proper operating discharge pressure.
The fan cycling control closes on an increase in
discharge pressure and opens on a decrease in
discharge pressure.
Check Procedure
1. Verify fan motor windings are not open or grounded
and fan spins freely.
2. Connect a manifold gauge set to the ice machine.
3. Hook a voltmeter in parallel across the fan cycle
control, leaving wires attached.
4. Refer to chart below:
Model
Cut-In (Close)
Cut-Out (Open)
QF0800
QC0700
250 psig +/- 5
200 psig+/- 5
Discharge
Pressure:
Reading Should Be:
Fan Should Be:
above cut-in
0 volts
running
below cut-in
line voltage
off
Revised 8/2003
Содержание QC0700
Страница 8: ...Table of Contents continued 6 Part No 80 1214 3 Revised 8 2003 ...
Страница 12: ...General Information Section 1 1 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 30: ...Installation Instructions Section 2 2 18 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 52: ...Ice Machine Sequence of Operation Section 4 4 4 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 122: ...Electrical System Section 6 6 60 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...
Страница 144: ...Refrigeration System Section 7 7 22 Part No 80 1214 3 Using Pinch Off Tool SV1406 Revised 8 2003 ...
Страница 147: ...Revised 8 2003 ...
Страница 150: ...Refrigeration System Section 7 7 26 Part No 80 1214 3 THIS PAGE INTENTIONALLY LEFT BLANK Revised 8 2003 ...