IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
21
6. Option Related Drive Parameters
The following parameters are used to set up the drive for operation with the Profinet card. Parameter
setting instructions can be found in the drive’s Instruction Manual.
Confirm proper setting of the all parameters in Table 5: Parameter Settings before starting network
communications.
Table 5: Parameter Settings
Parameter
Code
Display
Function
Range
Initial Value
B03-01
<1>
Ref Source 1
Source from where the frequency
reference is generated.
0–4
1 (Set to 3 for
PROFINET)
0
Operator
Digital Operator
1
Terminals
Terminals or Analog Input
•
S4-IF Interface Card
•
S4-I AC Digital Input Option
•
S4-IO Digital Input/Output Option
•
DI-A3 Digital Input Option (not used for
B03-02)
2
Serial Com
Serial communication
•
RS485/422 Serial Communications
(R+, R-, S+, S-)
3
Option PCB
Industrial Communication Option
card (Port CN5-A)
•
EtherNet/IP
•
Modbus TCP/IP
•
PROFINET
•
PROFIBUS-DP
4
Pulse Input
Pulse input via Terminal RP (H06-
01)
<1> To start and stop the drive with the option master device using serial communications, set B03-02 to 3. To control the drive frequency
reference via the master device, set B03-01 to 3.
<2> If F06-01 is set to 4: Alarm Only, then the drive will continue to operate when a bUS error or an EF0 fault is detected. Take proper
safety measures, such as installing an emergency stop switch.