![Magnetek IMPULSE G Plus Series 4 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/magnetek/impulse-g-plus-series-4/impulse-g-plus-series-4_installation-manual_3663700043.webp)
IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
43
Option Low Priority Alarm Codes
These codes are transmitted as Manufacturer Specific Diagnostic low priority alarms that can be
seen in the PLC configuration software. These low priority codes are the same codes that appear in
the drive manual, except with an offset of 0x0400.
Table 26: PROFINET Option Low Priority Alarm Codes
Drive Alarm
Code (hex)
<1>
Description
Drive Alarm
Code (hex)
<1>
Description
0401
Undervoltage (Uv)
042E
Maintenance Required Alert (MNT)
0402
Overvoltage (ov)
042F
Klixon Circuit Alarm (KLX)
0403
Heatsink Overhead (oH)
0431
Option Watchdog Error (E5)
0404
Drive Overheat (oH2)
0432
Option Station Address Setting Error (AEr)
0405
Overtorque 1 (OT1)
0433
Option Comm. Cycle Setting Error (CyC)
0406
Overtorque 2 (OT2)
0434
High Current Alarm (HCA)
0407
Run Command Input Error (EF)
0435
Cooling Fan Maintenance Time (LT-1)
0408
Drive Baseblock (bb)
4036
Capacitor Maintenance Time (LT-2)
0409
External Fault 3, input terminal S3 (EF3)
0438
Option EEPROM Error (EEP)
040A
External Fault 4, input terminal S4 (EF4)
0439
External Fault (input terminal S1) (EF1)
040B
External Fault 5, input terminal S5 (EF5)
043A
External Fault (input terminal S2) (EF2)
040C
External Fault 6, input terminal S6 (EF6)
043B
Safe Disable Input (HbbF)
040D
External Fault 7, input terminal S7 (EF7)
043C
Safe Disable Input (Hbb)
040E
External Fault 8, input terminal S8 (EF8)
043D
Mechanical Weakening Detection 1 (oL5)
040F
Cooling Fan Error (FAn)
043E
Mechanical Weakening Detection 2 (UL5)
0410
Overspeed (oS)
043F
PLC Alarm (PA1)
0411
Excessive Speed Deviation (dEv)
0440
PLC Alarm (PA2)
0412
PG Disconnected (PGO15)
0441
Output Voltage Detection Fault (voF)
0414
MEMOBUS/Modbus Comm. Error (CE)
0442
IGBT Maintenance Time (90%) (TrPC)
0415
Option Communication Error (bUS)
0443
Soft Charge Bypass Relay Maintenance
Time (LT-3)
0416
Serial Comm. Transmission Error (CALL)
0444
IGBT Maintenance Time (50%) (LT-4)
0417
Motor Overload (oL1)
0445
Braking Transistor Overload (boL)
0418
Drive Overload (oL2)
0448
Motor Overheat (NTC Input) (oH5)
041A
Option Card External Fault (EF0)
0449
Load Check (LC)
041B
Motor Switch Command Input during Run
(rUn)
044A
Upper Limit 3 Error (UL3)
041D
Serial Comm. Transmission Error (CALL)
044B
Upper Limit 2 Error (UL2)
041E
Undertorque Detection 1 (UT1)
044C
Lower Limit 2 Error (LL2)
041F
Undertorque Detection 2 (UT2)
044E
Upper Limit 1 Error (UL1)
0420
MEMOBUS/Modbus Test Mode Fault (SE)
044F
Lower Limit 1 Error (LL1)
0422
Motor Overheat (oH3)
0450
Brake Answer Lost (BE0)
0427
PID Feedback Loss (FbL)
0451
Brake Answer 1 (BE4)
0428
PID Feedback Loss (FbH)
0452
Brake Answer 2 (BE5)
042A
Drive Disabled (dnE)
0453
Brake Stop (BE6)
042B
PG Disconnected (PGO1H)
0454
Brake Slipping (BE8)
042D
Slack Cable Fault (SLC)
<1> Drive error code is stored in MEMOBUS/Modbus address 0080 hex.