IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
9
4. Option Components
SI-EP3 PROFINET Option
<1> The ground wire provided in the option shipping package must be connected during installation.
<2> Refer to Option LED Display on page 10 for details on the LEDs.
Figure 1: Option (Top View)
Terminal CN1
The communication connector on the option is a modular RJ45 female connector designated CN1.
CN1 is the connection point for a customer-supplied male Ethernet network communication cable.
Table 1: Male 8-way Ethernet Modular Connector (Customer-Supplied)
Male EtherNet 8-Way Modular
Connector
Pin
Description
1 (Pair 2)
Transmit data (TXD) +
2 (Pair 2)
Transmit data (TXD) -
3 (Pair 3)
Receive data (RXD) +
4 (Pair 1)
Not used <1>
5 (Pair 1)
Not used <1>
6 (Pair 3)
Receive data (RXD) -
7 (Pair 4)
Not used <1>
8 (Pair 4)
Not used <1>
<1> Not used for 10 Mbps and 100 Mbps networks.