Technical data
13
© Lutz-Jesco GmbH 2020
Subject to technical changes.
200116
BA-42840-02-V03
Water sampling station
EASYPRO COMPACT
Operating instructions
5.4 Multi-channel controller TOPAX
®
MC measuring inputs
Measuring inputs (depending on version)
Number of measuring inputs
up to 4
Free chlorine
Amperometric 3-electrode measur-
ing cell with potentiostat (DMZ3.1)
mg/l
0 – 15 (dependant on the measuring cell transconductance)
CS120 excess chlorine measuring cell
mg/l
0 – 10 (dependant on the measuring cell transconductance)
Diaphragm-covered measuring cell
mg/l
0 – 10 (dependant on the measuring cell)
Chlorine dioxide
Amperometric 3-electrode measur-
ing cell with potentiostat (DMZ3.1)
mg/l
0 – 15 (dependant on the measuring cell transconductance)
CS120 excess chlorine measuring cell
mg/l
0 – 10 (dependant on the measuring cell transconductance)
Diaphragm-covered measuring cell
mg/l
0 – 2 (dependant on the measuring cell)
Total chlorine
Diaphragm-covered measuring cell
mg/l
0 – 10 (dependant on the measuring cell)
pH value
pH single-rod measuring cell
pH
0 – 14 (dependant on the single-rod measuring chain)
Redox value
Redox single-rod measuring cell
mV
0 – 1000 (dependant on the single-rod measuring chain)
Temperature
Pt100
°C
-10 to +90
Tab. 12: Measuring inputs
TOPAX
®
MC
multi-channel controller
5.5 Multi-channel controller TOPAX
®
MC output modules
Output modules (depending on version)
Servomotor relay
2 x 230 V AC, 5 A (ohmic load)
kΩ
Potentiometer feedback: 1 – 10
Servomotor 20 mA
Constant 0/4 – 20 mA output
Servomotor with 20 mA feedback
Relays
2 x 230 V AC, 5 A (ohmic load)
Optocoupler
2 x 80 V DC, 5 mA
Tab. 13: Output modules
TOPAX
®
MC multi-channel controller