Step
Sensor Selection
Wiring the Daylight Sensor
•
Wire color designations of the daylight sensor:
Red = 20VDC
Black = Common
White = IR Signal
Yellow = Daylight Sensor Signal
•
Make sure that the supply breaker
to the digital ballast is OFF when wiring
•
Connect the four conductors to the
four digital ballast terminals as shown
Note: The digital ballast accepts only
one IR input. Use of the IR input
for the daylight sensor precludes
the use of an infrared receiver
with the same digital ballast.
Pendant Fixture
Ceiling Tile or Fixture
2
Daylight Sensor
with IR Receiver
Arrow points toward the area
viewed by the sensor
Bottom of sensor
1-2 H
H
3' (0.9m)
H = Effective Window Height
Ballast Terminals
Pendant Fixture
Ceiling Tile or Fixture
Red
Black
White
Yellow
White
Orange
Black
E1
E2
+20V
+20V
+20V
Common
Common
Common
IR
Occ
Daylight
Mounting the Daylight Sensor
Determine the proper location of the daylight
sensor using the adjacent diagrams.
•
The arrow on the daylight sensor points
toward the area viewed by the sensor
•
Place the daylight sensor so its viewing area
is centered upon the nearest window at a
distance of between 1-2 H from the window
•
The effective window height, H, starts
3' (0.91m) up from the floor or at the window
sill, whichever is higher, and ends at the top
of the window
•
Ensure that the view of the daylight sensor
is not obstructed
•
Do not position the daylight sensor in the well
of a skylight or above indirect lighting fixtures
Ballasts
BMF
Daylight
Sensors
Occupancy
Sensors
IR Receiver
and Remote
Bus Supply
1
2
3
4
2
1
W
allstations
3
Pr
ogrammer
4
Lutron
|
09
Technical Support:
1.800.523.9466 … 24 hours/7 days (US/CAN)
To Order:
1.888.LUTRON1 … 8 am – 8 pm/M-F ET (US/CAN)
22 AWG solid 105˚C only
EcoSystem
™
|
daylight sensors