EcoSystem Daylight Sensor with IR Receiver
C-SR-M1-WH
•
Automatically dim the lights when the available daylight
is high and brighten the lights when the available daylight
is low in order to maintain a specific light level in the space
•
Integrated IR receiver for EcoSystem programming
•
1 daylight sensor can control multiple fixtures or groups
of fixtures differently
•
Up to 8 daylight sensors can exist on a single EcoSystem bus
•
Total wire length to ballast (or BMF) must not
exceed 100' (30m)
•
Designed for Class 2 operation only
•
Operating voltage: Low-voltage Class 2, 20VDC
•
Analog signal: 0 – 20VDC
•
Daylight (photo) sensors from other manufacturers
are not compatible with EcoSystem
Step
Sensor Selection
Daylighting
Design Statement: Use 1 daylight sensor for each zone of fenestration.*
If the zone extends more than 30' (9.14m), include a daylight sensor for
every 30' (9.14m) segment.
Wiring a daylight sensor to one ballast allows
control of multiple ballasts on a bus.
2
Dimensions
H: 0.69" (17mm)
D: 1.18" (30mm)
Stem Length: 1.25" (32mm)
H
08
|
Lutron
www.lutron.com/ecosystem Lutron World Headquarters:
1.610.282.3800
* Fenestration: Any opening in a building’s envelope including windows, doors and skylights.
EcoSystem
™
|
daylight sensors
Содержание EcoSystem