There are two different ways that EcoSystem can integrate
with Emergency systems.
Emergency Situation:
No power is lost
Normal power is lost
Emergency Result
An emergency signal can
All ballasts will turn off except
be sent from a building
ballasts that are fed by the
management system or
emergency power source (i.e.
emergency system to the
generator, battery) as shown in
contact closure on the
the wiring diagram. The ballasts
EcoSystem bus supply. All
receiving emergency power will
ballasts on the bus will respond
go to 100% unless programmed
by going to 100%, unless
to do otherwise.
programmed to do otherwise.
Emergency
Generator or
Emergency
Feed
Normal Service
Distribution Panel
Normal/Emergency
Service Distribution Panel
To Normal Loads
(Non-Emergency)
Normal Service Feeds
Normal/Emergency Service Feeds
Emergency Transfer Switch (by others).
Must be UL 1008 listed as
emergency transfer relay.
To Normal/Emergency Loads
Bus Supply
Bus Wiring
E
Lutron
|
25