Limits
Each EcoSystem bus can
accommodate the following:
•
64 Ballasts/BMFs
•
32 Occupancy Sensors
•
64 Wallstations or
Infrared Sensors
•
8 Daylight Sensors
4
4
16
|
Lutron
www.lutron.com/ecosystem Lutron World Headquarters:
1.610.282.3800
EcoSystem Bus Supply
Design Statement: The EcoSystem bus supply is required for two
or more ballasts (or BMFs) to work together. The bus supply powers
the communication bus and is capable of supporting up to 64 ballasts
or BMFs. For integration of multiple bus supplies or other lighting
control systems, please contact a Lutron Representative.
EcoSystem Digital Bus Supply
CS-1L-CM
(shown)
Contractor mountable, no enclosure,
2 contact closures, 1 panic contact closure
CS-1L-WM
2 contact closures, 1 panic contact closure, 1 wallstation/
IR connection, wall-mountable inside enclosure
•
Accepts one panic normally open or normally closed
dry contact closure to override light level to full output
•
EcoSystem bus may be wired Class 1 or Class 2;
bus wires are polarity insensitive
•
Topology-free wiring; Bus supply may be wired to the
communication bus at any point
•
Output voltage: 16VDC 250 mA Max (Class 1 or Class 2)
•
Powered by 120 or 277 V, ~50 or 60 Hz
•
Bus supply terminals:
- EcoSystem bus: #12 – #18 AWG (2.05 – 1.02mm) Solid
- Power wiring: #12 – #18 AWG (2.05 – 1.02mm) Solid
- Class 2 contact closures
•
Non-volatile (EEPROM) memory stores system programming
for 10 years from power down to power restored
•
Lutron recommends 1 bus supply for each room being
controlled by EcoSystem
•
Power draw is < 0.12 A; can be fed with same circuit as fixtures
Step
Support Components
EcoSystem
™
|
bus supply
Dimensions
W: 1.77" (45mm)
H: 3.56" (85mm)
D: 3.62" (92mm)