46/70
“LS Ubiquitous RF-ID System”
[Table 4.2.1.4] Receiving Frame Structure: normal operation
No.
1
2
3
4
5
6(LSB)
7
Des-
cription
Start
Byte
(F0)
Station ID
(SID)
Length
(DL)
Control
Mode
Error
Code
0x00
Determined by
Command 1,2
Check Sum
(CS)
[Table 4.2.1.5] Description of each item of Normal Receiving Frame
No.
Items
Description
1
Start Byte
Byte indicating the start of Receiving Frame (displayed as F0)
2
Station ID
Station no. given to Reader (which adjusts the value of Rotary
switch next to Reader.)
3
Data Length
Total length of Frame (from Start Byte to Check Sum)
4
Control Mode
Mode to select the control environment of Reader
5
Error Code
At normal receiving frame, ‘00’
6
LSB
Determined by Command and Control value
7
Check Sum
Check Sum value
[Table 4.2.1.6] below shows the Receiving Frame Structure when error occurred if Reader
performed abnormal communication operation. And [Table 4.2.1.7] shows the description of
each item of Frame Structure where error occurred by abnormal receiving.
[Table 4.2.1.8] shows Error Code indicated in Receiving Frame when error occurs.
[Table 4.2.1.6] Receiving Frame Structure: when Error occurs
No.
1
2
3
4
5
6
7
Des-
cription
Start Byte
(F0)
Station ID
(SID)
Length
(DL)
Control
Mode
Error
Code 1
Error
Code2
Check Sum
(CS)
Содержание LGRF-H
Страница 23: ...23 70 LS Ubiquitous RF ID System 2 4 Product Appearance and Dimension Fig 2 4 1 LGRF H Reader...
Страница 24: ...24 70 LS Ubiquitous RF ID System Fig 2 4 2 LGRF H Reader Fig 2 4 3 Antenna A Type...
Страница 25: ...25 70 LS Ubiquitous RF ID System Fig 2 4 4 Antenna B Type Fig 2 4 5 Antenna C Type...
Страница 69: ...69 70 LS Ubiquitous RF ID System Appendix C PLC Examples 1 Example of MELSEC PLC HEX mode communication...
Страница 70: ...70 70 LS Ubiquitous RF ID System 2 Example of MELSEC PLC ASCII mode communication...