17
2.4 Refrigeration Circuit
2.4.1 Minimum pipe sizes (up to 15m), maximum length and maximum lift.
SYSTEM
MODEL
Liquid Line
mm (inches)
Suction Line
mm (inches)
Maximum Length
(m)
Maximum Lift
(m)
H-IV-7
9.5 (3/8”)
15.9 (5/8”)
25
10
H-IV-11
9.5 (3/8”)
15.9 (5/8”)
30
20
H-IV-15
9.5 (3/8”)
19 (3/4”)
50
20
H-DV-18
9.5 (3/8”)
19 (3/4”)
60
25
H-DV-22
12.7 (1/2”)
22.2 (7/8”)
60
25
H-DV-26
12.7 (1/2”)
25.4 (1”)
60
25
Minimum pipe sizes (up to 30m), factory charge and additional refrigerant required.
SYSTEM
MODEL
Liquid Line
mm (inches)
Suction Line
mm (inches)
Factory
Charge (kg)
ADD REFRIGERAnT
>15M (g/m)
H-IV-7
9.5 (3/8”)
15.9 (5/8”)
2.75
30
H-IV-11
9.5 (3/8”)
15.9 (5/8”)
2.75
30
H-IV-15
9.5 (3/8”)
19 (3/4”)
4.7
30
H-DV-18
12.7 (1/2”)
22.4 (7/8”)
6.3
60
H-DV-22
12.7 (1/2”)
25.4 (1”)
6.9
60
H-DV-26
15.9 (5/8”)
28.4 (1,1/8”)
7.3
100
2.3 Refrigeration pipes
• Maximum pipe length is 60 m. Extra oil (3GS refrigeration oil) is to be added for lengths over
30 m: - 30 ml per meter over 30 m.
• Lines must be sized correctly to ensure that pressure drops within the system are
minimised. Mechanics should refer to the above pipe sizing table prior to installation.
• Refrigeration grade copper tubing is the only tubing to be used. Fittings used for bends,
elbow, ‘P’ trap, ‘Y’ piece, etc., must be of the wrought copper type and clean from dust,
burrs, oil, etc. It is recommended that the tube is cut with a tube cutter and the entire
ID is made the correct size with an expanding device after cutting. All joints in the piping
must be clean and free from dust, burrs, oil, etc.
• All joints must be silver soldered with at least 10% silver content.
Содержание Bravo H-DIG-18
Страница 9: ...9 2 2 2 VAV Series Drawings H VAV 7...
Страница 10: ...10 H VAV 11...
Страница 11: ...11 H VAV 15...
Страница 12: ...12 H VAV 18...
Страница 13: ...13 1314 1550 81 487 60 410 601 60 300 H VAV 22 H VAV 26...
Страница 14: ...14 2 2 2 Radical Flow Series Drawings H RAD 22 H RAD 26 H RAD 15 H RAD 18...
Страница 21: ...21 Indoor Electrical Connection Diagram H VAV 22 26...
Страница 22: ...22 Indoor Electrical Connection Diagram H RAD 18 22 26 Indoor Electrical Connection Diagram H RAD 11 15 18...
Страница 56: ...56 Livezi Phone 1300 306 125 Fax 07 3870 8270 Web www livezi com au Email info livezi com au...