15
2.3 Duct Circuit
2.3.1 VAV Series Duct Layout Requirements
• Duct pressure operating range of the VAV series indoor units is 60 Pa ~ 200 Pa.
• Care should be taken to minimise changes in speed or direction.
• Care should be taken to keep the velocity within supply ducts below 6 m/s.
• Fan and coil can be split to meet structural challenges.
Содержание Bravo H-DIG-18
Страница 9: ...9 2 2 2 VAV Series Drawings H VAV 7...
Страница 10: ...10 H VAV 11...
Страница 11: ...11 H VAV 15...
Страница 12: ...12 H VAV 18...
Страница 13: ...13 1314 1550 81 487 60 410 601 60 300 H VAV 22 H VAV 26...
Страница 14: ...14 2 2 2 Radical Flow Series Drawings H RAD 22 H RAD 26 H RAD 15 H RAD 18...
Страница 21: ...21 Indoor Electrical Connection Diagram H VAV 22 26...
Страница 22: ...22 Indoor Electrical Connection Diagram H RAD 18 22 26 Indoor Electrical Connection Diagram H RAD 11 15 18...
Страница 56: ...56 Livezi Phone 1300 306 125 Fax 07 3870 8270 Web www livezi com au Email info livezi com au...