24
• Fan Speed
Default = 100%
The fan speed may be adjusted from 100% to 30%
• Runtimer
Default = Disabled
The runtimer counts down run hours from a preset limit. At the end of the timer period the
system switches off.
REAL TIME CLOCK
The REAL TIME CLOCK enables the use of up to 15 individual timer programs to schedule when
the system switches on and off. Refer to the CENTRAL operating instructions for details.
3.1.1 Sensor selection
Temperature is measured from a single location - either from the sensor mounted on the
touchpad, or a sensor directly connected to the indoor unit control module (generally located in
the return air duct).
When using the touchpad mounted sensor, the touchpad is typically located 1.5 m above floor
level near the return air grille.
When using the return air sensor input on the indoor unit controller, the touchpad(s) may be
mounted in the most convenient location.
To enable use of the touchpad onboard sensor, DIP switch 1 on the back of the touchpad must
be set to the on position. If there are multiple touchpads, only one LCD touchpad can have
the onboard sensor enabled. If the touchpad sensor is enabled, make sure there is no sensor
connected to the indoor unit controller
LCD Plant Control Touchpad DIP switches
DIP switch #
Function
OFF
F
actory
D
eFault
On
1
Onboard sensor
D
isableD
Enabled
2
Not Used
-
-
3
Not Used
-
-
4
Not Used
-
-
Содержание Bravo H-DIG-18
Страница 9: ...9 2 2 2 VAV Series Drawings H VAV 7...
Страница 10: ...10 H VAV 11...
Страница 11: ...11 H VAV 15...
Страница 12: ...12 H VAV 18...
Страница 13: ...13 1314 1550 81 487 60 410 601 60 300 H VAV 22 H VAV 26...
Страница 14: ...14 2 2 2 Radical Flow Series Drawings H RAD 22 H RAD 26 H RAD 15 H RAD 18...
Страница 21: ...21 Indoor Electrical Connection Diagram H VAV 22 26...
Страница 22: ...22 Indoor Electrical Connection Diagram H RAD 18 22 26 Indoor Electrical Connection Diagram H RAD 11 15 18...
Страница 56: ...56 Livezi Phone 1300 306 125 Fax 07 3870 8270 Web www livezi com au Email info livezi com au...