LTC3882-1
85
Rev A
MFR_TEMP_1_GAIN
The MFR_TEMP_1_GAIN command sets the slope used in the calculation of external temperature to account for non-
idealities in the element and remote sensing errors, if any. Refer to the MFR_PWM_MODE_LTC3882-1 command for
equation details.
This command has two data bytes representing a 2’s complement integer.
MFR_TEMP_1_OFFSET
The MFR_TEMP_1_OFFSET command sets the offset used in the calculation of external temperature to account for
non-idealities in the element and remote sensing errors, if any. The unit of measure for MFR_TEMP1_OFFSET depends
on bit 5 of MFR_PWM_MODE. MFR_TEMP1_ OFFSET is expressed volts if this bit is set and in °C otherwise. Refer to
the MFR_PWM_MODE_ LTC3882-1 command for equation details.
This command has two data bytes in Linear_5s_11s format.
OT_FAULT_LIMIT
The OT_FAULT_LIMIT command sets the value of sensed external temperature, in degrees Celsius, which causes an
overtemperature fault.
This command has two data bytes in Linear_5s_11s format.
OT_WARN_LIMIT
The OT_WARN_LIMIT command sets the value of sensed external temperature, in degrees Celsius, which causes an
overtemperature warning. If the OT_WARN_LIMIT is exceeded, the device:
• Sets the TEMPERATURE Bit in the STATUS_BYTE
• Sets the Overtemperature Warning Bit in the STATUS_TEMPERATURE Command
• Notifies the Host by Asserting
ALERT
, Unless Masked
This command has two data bytes in Linear_5s_11s format.
EXTERNAL TEMPERATURE AND LIMITS
COMMAND NAME
CMD
CODE DESCRIPTION
TYPE
PAGED
DATA
FORMAT UNITS NVM
DEFAULT
VALUE
MFR_TEMP_1_GAIN
0xF8 Set slope for external temperature
calculations.
R/W Word
Y
CF
l
1.0
0x4000
MFR_TEMP_1_OFFSET
0xF9 Offset addend for external temperature
calculations.
R/W Word
Y
L11
°C or V
l
0.0
0x8000
OT_FAULT_LIMIT
0x4F External overtemperature fault limit.
R/W Word
Y
L11
°C
l
100.0°C
0xEB20
OT_WARN_LIMIT
0x51 External overtemperature warning limit.
R/W Word
Y
L11
°C
l
85.0°C
0xEAA8
UT_FAULT_LIMIT
0x53 External undertemperature fault limit.
R/W Word
Y
L11
°C
l
–40.0°C
0xE580
Related commands: STATUS_TEMPERATURE, SMBALERT_MASK, MFR_TEMPERATURE1_PEAK, OT_FAULT_RESPONSE, UT_FAULT_RESPONSE,
STATUS_MFR_SPECIFIC, READ_TEMPERATURE_2, MFR_OT_FAULT_RESPONSE, MFR_PWM_MODE_LTC3882-1
PMBus COMMAND DETAILS
(External Temperature and Limits)