14
AHU CONTROL KIT SETTINGS
ENGLISH
EEV Module
(EEV Module)
Capacity Settings
Use DIP switch SW1 to set the capacity.
* When connecting a high-capacity EEV kit (PRLK396A0, PRLK594A0), set the capacity to
56.4 kW.
Address Setting
DIP switch SW2 is the address setting function. When the product is shipped from the factory,
the addresses are set as follows.
EEV #1,2,3 are included and EEV #4,5,6 are optional.(After purchasing separately, additional
setting required.)
SW1
1
2
3
4
Capacity [kW (kBtu/h)]
OFF
OFF
OFF
OFF
2.1 (7)
OFF
OFF
OFF
ON
2.5 (9)
OFF
OFF
ON
OFF
3.5 (12)
OFF
OFF
ON
ON
5.6 (18)
OFF
ON
OFF
OFF
7.1 (24)
OFF
ON
OFF
ON
8.2 (28)
OFF
ON
ON
OFF
10.6 (36)
OFF
ON
ON
ON
12.3 (42)
ON
OFF
OFF
OFF
14.1 (48)
ON
OFF
OFF
ON
22.4 (76)
ON
OFF
ON
OFF
28.0 (96)
ON
OFF
ON
ON
33.6 (115)
ON
ON
OFF
OFF
39.2 (134)
ON
ON
OFF
ON
44.8 (153)
ON
ON
ON
OFF
50.5 (172)
ON
ON
ON
ON
56.4 (192)
Sequence
SW2
Address
Remark
1
2
3
4
EEV #1
OFF
OFF
OFF
OFF
Internal address 0
EEV #1,2,3
Included
EEV #2
OFF
OFF
ON
Internal address 1
EEV #3
OFF
ON
OFF
Internal address 2
EEV #4
OFF
ON
ON
Internal address 3
EEV #4,5,6 Optional :
Additional setting required
EEV #5
ON
OFF
OFF
Internal address 4
EEV #6
ON
OFF
ON
Internal address 5