HMI SETTINGS
33
ENGLISH
5-1-1. Air Conditioner Settings
• Run the 'Air Conditioner Settings' icon to set the air conditioner and operation.
Item
Description
Air conditioner type
Set air conditioner type: air conditioner,
dedicated outdoor air system
Temperature determination
criteria
Set target temperature criteria: return air,
supply air
- Return air criteria: cooling 18-30 °C , heating
16-30 °C
Supply air cooling target
temperature
Can be set when the target temperature criteria
is air supply (outdoor unit capacity control
operation)
- Set temperature 12-50 °C
Supply air heating target
temperature
Outdoor unit sequential control enable/disable
setting
Outdoor unit sequential
control
Outdoor unit simultaneous thermo-off
prevention function
Item
Description
Cooling
humidification
function
You can set the cooling humidification function.
Enabled when the 'Humidification' function is set in
Additional Operation mode.
Warming-up
time
You can set the warming-up operation time.
Warming-up operation only circulates indoor air with the
outdoor air and exhaust dampers closed so that the indoor
load can be quickly removed.
- Settable time: 0-180 minutes
Automatic
control address
You can set the automatic control address.
- Set to decimal
- Since ACP uses hexadecimal, set to decimal when
connecting ACP (ex, ACP: 0x29
→
address: 41).
- Settable address range: 1-247
Return air (RA)
fan count
Set the number of return air fans applied to the air
conditioner.
- Number of return air fans: 0, 1, 2, 4, 6
Supply air (SA)
fan count
Set the number of supply air fans applied to the air
conditioner.
- Number of return air fans: 0, 1, 2, 4, 6
CAUTION
!
• Correctly set the air conditioner type.
- An error could occur in sensors, damper actuators, etc.
• When setting the temperature determination criteria to air supply, be sure to connect the
capacity control communication.
- A communication error could occur.
• Outdoor unit sequential control is enabled when the temperature determination criteria is
return air.
CAUTION
!
• The number of set fans should match the number of fans installed to the air conditioner.
- If there is a discrepancy in the number of fans, operation and monitoring will not run
normally.