5-1-2. Device Setting
• Run the 'Device Setting' icon on the Installer Setting screen to enable device settings
required for air conditioner operation.
Item
Description
Return air (RA)
temperature/
humidity
Sets the sensors to be installed to the return air duct.
- Sensor type: Thermistor, temperature/humidity sensor
- A temperature or temperature/humidity sensor must be
installed on the return air side.
- Humidification operation is only available if a
temperature/humidity sensor is installed.
Supply air (SA)
temperature/
humidity
Sets the sensors to be installed on the supply air duct.
- Sensor type: Thermistor, temperature/humidity sensor
- A temperature or temperature/humidity sensor must be
installed on the supply air side.
Outdoor air
(OA)
temperature/
humidity
Sets whether temperature/humidity sensors are installed in
the outdoor air duct.
- If no outdoor air temperature/humidity sensor is installed,
dehumidification and outdoor air cooling will not be
possible.
Mixed (Mix)
temperature
Sets whether temperature sensors are installed in the
mixed chamber.
Static pressure
supply air (SA)
Sets whether static pressure sensors are installed on the
supply air side.
- When a static pressure sensor is installed, you can control
static pressure-based airflow.
Item
Description
Differential
pressure-filter
(alarm level)
Sets whether a filter differential pressure sensor is
installed.
- Differential pressure setting range: 200-600 Pa
- The filter alarm is displayed when the differential pressure
set value has been reached.
CO
2
Sets whether a CO
2
sensor is installed in the return air
duct.
- CO
2
setting range: 500-1,500 PPM
- When a CO
2
sensor is installed, automatic return air
operation is possible.
Return air flow
Sets whether a flow sensor is installed in the return air
duct.
Supply air flow
Sets whether a flow sensor is installed in the supply air
duct.
Damper
feedback
Sets whether the damper feedback function is enabled.
It is enabled when the feedback signal line of the damper
actuator is connected.
Item
Description
Preheating coil
Sets the heat source and whether the preheating coil is
enabled.
- Preheating heat source: electric heater, steam
Humidifier
Sets whether a humidifier is installed.
Содержание PAHCNM000