36
HMI SETTINGS
ENGLISH
5-1-3. Sensor Range Setting
• Run the 'Sensor Range Setting' icon on the Installer Setting screen to set the operating
range of the installed sensor.
Item
Description
Return air temperature
Sets the sensor range based on the
operating range of the installed
thermistor.
- minimum: -100-20 °C,
maximum: 0-127 °C
Supply air temperature
Outdoor air temperature
Mixed temperature
Static pressure-supply air (SA)
Sets the sensor range based on the
operating range of the installed static
pressure sensor.
- minimum: 0-200 Pa,
maximum: 200-1000 Pa
Item
Description
Differential
pressure-filter
(alarm level)
Sets the sensor range based on the operating range of the
installed differential pressure sensor.
- minimum: 0-200 Pa, maximum: 200-1000 Pa
Return air flow
Sets the sensor range based on the operating range of the
installed flow sensor.
- minimum: 0-20 m/s, maximum: 0-20 m/s
Supply air flow
Sets the sensor range based on the operating range of the
installed flow sensor.
- minimum: 0-20 m/s, maximum: 0-20 m/s
CO
2
Sets the sensor range based on the operating range of the
installed CO
2
sensor.
- minimum: 0-990 PPM, maximum: 1000-2000 PPM
5-1-4. Smoke Control Operation Setting
• Run the 'Smoke Control Operation
Setting' icon on the Installer Setting
screen to set the smoke control operation.
If the text “Fire” appears on the 7-Seg in
Smoke Control mode, it can be canceled
by entering LEFT (
←
) + RIGHT (
→
) +
DOWN (
↓
) + UP (
↑
) within 5 seconds.
Item
Description
Smoke Control
mode (smoke
detecting sensor)
Sets whether Smoke Control mode is enabled.
- Only available if a smoke detecting sensor is installed.
Outdoor air (OA)
damper
Sets the outdoor air damper operating status when in
Smoke Control mode.
- Fully open, Fully closed
Exhaust air (EA)
damper
Sets the exhaust air damper operating status when in
Smoke Control mode.
- Fully open, Fully closed
Mixed (Mix) damper
Sets the mixed damper operating status when in
Smoke Control mode.
- Fully open, Fully closed
Return Air Fan
Sets the operating Hz of the return air fan when in
Smoke Control mode.
- Setting range: 0-60 Hz