20
AHU SENSOR CONNECTION
ENGLISH
Ex: SA (Supply) Temperature/Humidity Sensor Connection
1. For more information on the installation of temperature/humidity sensors, refer to the
Manual that came with the sensor.
2. Make sure to finish all the sensor wires with a flexible tube.
3. Using a temperature/humidity sensor outside the temperature range different from the
above specifications can cause the unit to malfunction. However, the temperature range
can be adjusted in HMI Settings.
Item
Specification
Remark
Temperature/humidity
sensor
- Power: AC 24 V
- Output signal: DC 0~10 V
- Temperature range: -40 °C~70 °C
- Humidity range: 0~95 % RH
Optional
CAUTION
!
• Improper wiring of the sensor can damage the AHU CONTROL KIT. Make sure to check for
any incorrect wiring before turning the power on.
DC 0~10 V(Temperature,U1)
DC 0~10 V(Humidity,U2)
<Main module>
<Terminal block>
UI1
UI2
Ground (G0)
Ground (G0)
AC 24 V(G)
AC 24 V(G)