42
HMI SETTINGS
ENGLISH
No.
Address
Register
Data Bit
Notes
Hexadecimal
Decimal
1
0x0000
0
30001
AHU Version
AHU Controller's Version display [0.1] X
10
2
0x0001
1
30002
Error Air Conditioner
Error occurring AHU (fixed as 1)
3
0x0002
2
30003
Error Device
Error occurring devices (see error code)
4
0x0003
3
30004
Error Code
Corresponding device's error code
5
0x0004
4
30005
Total product operation time
(minutes, high)
Higher operating time data (Increases
operating time when operating based on
the supply fan) [min]
6
0x0005
5
30006
Total product operation time
(minutes, low)
Lower operating time data (Increases
operating time when operating based on
the supply fan) [min]
7
0x0006
6
30007
Number of connected outdoor
units
0~6 [ea]
11
0x000A
10
30011
Return air temperature
Temperature range (-99.9-99.9) [°C] X 10
12
0x000B
11
30012
Return air humidity
Humidity range (0-100.0) [%] X 10
13
0x000C
12
30013
Supply air temperature
Temperature range (-99.9-99.9) [°C] X 10
14
0x000D
13
30014
Supply air humidity
Humidity range (0-100.0) [%] X 10
15
0x000E
14
30015
Outdoor air temperature
Temperature range (-99.9-99.9) [°C] X 10
16
0x000F
15
30016
Outdoor air humidity
Humidity range (0-100.0) [%] X 10
17
0x0010
16
30017
Mixed temperature
Temperature range (-99.9-99.9) [°C] X 10
20
0x0013
19
30020
Cold water valve
Voltage range (0-10,000) [mV]
21
0x0014
20
30021
Hot water valve
Voltage range (0-10,000) [mV]
22
0x0015
21
30022
Co2 Concentration
Concentration range (0-2000) [ppm]
23
0x0016
22
30023
Static pressure sensor pressure
Pressure range (0-1000) [Pa]
24
0x0017
23
30024
Differential pressure sensor
pressure
Pressure range (0-1000) [Pa]
25
0x0018
24
30025
Outdoor air damper current value
Opening range (0-90) [˚]
26
0x0019
25
30026
Exhaust air damper current value
Opening range (0-90) [˚]
27
0x001A
26
30027
Mixed damper current value
Opening range (0-90) [˚]
31
0x001E
30
30031
Return air FAN 1 operating
frequency
Frequency range (0-60) [Hz]
32
0x001F
31
30032
Return air FAN 2 operating
frequency
Frequency range (0-60) [Hz]
33
0x0020
32
30033
Return air FAN 3 operating
frequency
Frequency range (0-60) [Hz]
High
Low