HMI SETTINGS
41
ENGLISH
• Coil Register
• Discrete Register
No.
Address
Register
Data Bit
Notes
Hexadecimal
Decimal
1
0x0000
0
1
Operation Setting
0: Off / 1: On
2
0x0001
1
2
Automatic return air (additional operation)
0: Off /
1: Automatic return air
3
0x0002
2
3
Humidification function (additional operation)
0: Off / 1: Humidification
High
Low
No.
Address
Register
Data Bit
Notes
Hexadecimal
Decimal
1
0x0000
0
10001
Return air fan operating status
0:Off, 1:On
2
0x0001
1
10002
Supply air fan operating status
0:Off, 1:On
3
0x0002
2
10003
Preheating heater status
0:Off, 1:On
9
0x0008
8
10009
Alarm Level1
0:Normal, 1:Alarm
10
0x0009
9
10010
Alarm Level2
0:Normal, 1:Alarm
11
0x000A
10
10011
Alarm Level3
0:Normal, 1:Alarm
12
0x000B
11
10012
Smoke detection
0:Normal, 1:Alarm
13
0x000C
12
10013
Filter Replacement
0:Normal, 1:Alarm
14
0x000D
13
10014
Filter Not Replaced Alarm
Occurs 300 hours after the
filter replacement alarm
17
0x0010
16
10017
Return Air FAN 1 Operating Status
0:Off, 1:On
18
0x0011
17
10018
Return Air FAN 2 Operating Status
0:Off, 1:On
19
0x0012
18
10019
Return Air FAN 3 Operating Status
0:Off, 1:On
20
0x0013
19
10020
Return Air FAN 4 Operating Status
0:Off, 1:On
21
0x0014
20
10021
Return Air FAN 5 Operating Status
0:Off, 1:On
22
0x0015
21
10022
Return Air FAN 6 Operating Status
0:Off, 1:On
23
0x0016
22
10023
Reserved
24
0x0017
23
10024
Reserved
25
0x0018
24
10025
Supply Air FAN 1 Operating Status
0:Off, 1:On
26
0x0019
25
10026
Supply Air FAN 2 Operating Status
0:Off, 1:On
27
0x001A
26
10027
Supply Air FAN 3 Operating Status
0:Off, 1:On
28
0x001B
27
10028
Supply Air FAN 4 Operating Status
0:Off, 1:On
29
0x001C
28
10029
Supply Air FAN 5 Operating Status
0:Off, 1:On
30
0x001D
29
10030
Supply Air FAN 6 Operating Status
0:Off, 1:On
33
0x0020
32
10033
Outdoor Unit 1 Operating Status
0:Off, 1:On
34
0x0021
33
10034
Outdoor Unit 2 Operating Status
0:Off, 1:On
35
0x0022
34
10035
Outdoor Unit 3 Operating Status
0:Off, 1:On
36
0x0023
35
10036
Outdoor Unit 4 Operating Status
0:Off, 1:On
39
0x0026
38
10039
Reserved
40
0x0027
39
10040
Reserved
41
0x0028
40
10041
Outdoor Unit 1 Defrost Status
0:No function, 1:Defrost
42
0x0029
41
10042
Outdoor Unit 2 Defrost Status
0:No function, 1:Defrost
43
0x002A
42
10043
Outdoor Unit 3 Defrost Status
0:No function, 1:Defrost
44
0x002B
43
10044
Outdoor Unit 4 Defrost Status
0:No function, 1:Defrost
High
Low
Содержание PAHCNM000
Страница 50: ...50 ENGLISH ...
Страница 51: ......