24
AHU SENSOR CONNECTION
ENGLISH
- CO
2
sensor
Ex: CO
2
Sensor Connection
1. For more information on the installation of CO
2
sensors, refer to the Manual that came
with the sensor.
2. Make sure to finish all the sensor wires with a flexible tube.
3. The setting for the CO
2
sensor can be changed in the setting section of the HMI.
Item
Specification
Remark
CO
2
sensor
- Power: AC 24 V
- Output Signal: DC 0~10 V
- Range: 0~2 000 ppm
Optional
CAUTION
!
• Improper wiring of the sensor can damage the AHU CONTROL KIT. Make sure to check for
any incorrect wiring before turning the power on.
UI3
DC 0~10 V(Y, Feedback)
<Terminal block>
<UI module>
Ground (G0)
Ground (G0)
AC 24 V(G)
AC 24 V(G)