11. Test Run
50
Installation of Outside Units
11.6 Maintenance/Repair checklist
(
̻
: Check mark)
CAUTION
• The above checklist is set based on the minimum period and more frequent checking can be required depending
on the operating condition/water quality condition.
• When cleaning the heat exchanger, make sure to take parts out or lock the value so that chemical detergent
does not penetrate into the pressure gauge etc.
• When cleaning the heat exchanger, check the connecting part of the water pipes prior to cleaning so that the
chemical detergent does not leak.
• After sufficiently mixing the chemical detergent with water, start cleaning.
• Cleaning the heat exchanger is easier at the initial stage and becomes difficult after the scaling has
accumulated.
• In areas where the water quality is poor, cleaning is required periodically.
Because chemical detergent has strong acidity, it must be washed off thoroughly with water.
• To check whether it is cleaned well inside, remove the hose and check the inside.
• Purge the air to remove any air inside the water pipe.
• After checking, always check whether the heat water supply is flowing normally flowing before operating the
product.
Checkpoint
Period (Year)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Product operating condition
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
Heat exchanger cleaning (Wash)
̻
̻
̻
Strainer cleaning
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
Water quality check
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
Refrigerant leakage check
̻
̻
Indoor unit filter cleaning
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
̻
Содержание MULTI V WATER IV ARWN080LAS4
Страница 1: ...Heat Pump 380 415V 380V R410A 50Hz 60Hz 0CVW0 01N Replaces 0CVT0 01M P No MFL61741615 ...
Страница 27: ...17 MULTI V Water IV Heat Pump Outside Units 4 Wiring Diagrams ARWN080LAS4 ARWN100LAS4 ARWN140LAS4 ...
Страница 28: ...MULTI V Water IV Heat Pump 4 Wiring Diagrams 18 Outside Units ARWN200LAS4 ...
Страница 392: ...Special Guide MULTI V Water IV Heat Pump 1 Cautions for Refrigerant Leaks ...