MULTI V Water IV
Heat Pump
6. Installation
10
Installation of Outside Units
Step 2) Burrs removal
• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs
drop in the tubing.
Step 3) Flaring work
• Carry out flaring work using flaring tool as shown below.
[Unit:mm]
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Step 4) Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared section and do flaring work again
Indoor unit
[kW(Btu/h]
Pipe
" A "
Gas
Liquid
Gas
Liquid
˺
5.6(19,100)
Ø12.7
Ø6.35
1.6~1.8
1.1~1.3
<16.0(54,600)
Ø15.88
Ø9.52
1.6~1.8
1.5~1.7
˺
22.4(76,400)
Ø19.05
Ø9.52
1.9~2.1
1.5~1.7
Pipe
Reamer
Point down
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =