6. Electrical Characteristics
23
MULTI V Water IV
Heat Pump
Outside Units
50Hz
Model
Unit
Power supply
Comp
Hz
Volts
Voltage-range
MCA
MFA
TOCA
MSC
RLA(Cooling)
RLA(Heating)
8HP
50
380-415
Min.:342,Max:456
17.9
25
24
-
6.31
6.86
10HP
50
380-415
Min.:342,Max:456
18.6
25
24
-
8.32
8.72
14HP
50
380-415
Min.:342,Max:456
20.0
25
24
-
12.81
13.35
20HP
50
380-415
Min.:342,Max:456
29.0
35
32
-
18.3
19.07
16HP
50
380-415
Min.:342,Max:456
35.8
50
48
-
12.61
13.72
18HP
50
380-415
Min.:342,Max:456
36.5
50
48
-
14.62
15.59
22HP
50
380-415
Min.:342,Max:456
37.9
50
48
-
19.11
20.21
24HP
50
380-415
Min.:342,Max:456
38.6
50
48
-
21.12
22.07
28HP
50
380-415
Min.:342,Max:456
40.0
50
48
-
25.62
26.69
30HP
50
380-415
Min.:342,Max:456
47.6
60
56
-
26.61
27.79
34HP
50
380-415
Min.:342,Max:456
49.0
60
56
-
31.11
32.41
40HP
50
380-415
Min.:342,Max:456
58.0
70
64
-
36.59
38.13
42HP
50
380-415
Min.:342,Max:456
66.9
85
80
-
37.41
39.27
44HP
50
380-415
Min.:342,Max:456
67.6
85
80
-
39.42
41.14
48HP
50
380-415
Min.:342,Max:456
69.0
85
80
-
43.91
45.76
50HP
50
380-415
Min.:342,Max:456
76.6
95
88
-
44.91
46.85
54HP
50
380-415
Min.:342,Max:456
78.0
95
88
-
49.40
51.48
60HP
50
380-415
Min.:342,Max:456
87.0
105
96
-
54.89
57.20
62HP
50
380-415
Min.:342,Max:456
95.9
120
112
-
55.71
58.34
64HP
50
380-415
Min.:342,Max:456
96.6
120
112
-
57.72
60.20
68HP
50
380-415
Min.:342,Max:456
98.0
120
112
-
62.21
64.83
70HP
50
380-415
Min.:342,Max:456
105.6
130
120
-
63.21
65.92
74HP
50
380-415
Min.:342,Max:456
107.0
130
120
-
67.70
70.54
80HP
50
380-415
Min.:342,Max:456
116.0
140
128
-
73.19
76.26
Note
1. Voltage supplied to the unit terminals should be within the minimum and maximum range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM are measured as the outdoor unit test condition.
6. TOCA means the total over current value of each outdoor unit.
7. Select the wire size based on the larger value among MCA or TOCA.
8. MFA is used to select the circuit breaker and ground fault circuit interrupter, and all
installation site must requirement attachment of an earth leakage breaker.[circuit breaker
type is ELCB (Earth Leakage Circuit Breaker)].
9. Select the electrical equipment of combination unit according to the electrical characteristics
of individual unit.
Symbols
MCA :
Minimum Circuit Amperes (A)
TOCA :
Total Over Current Amperes (A)
MFA :
Maximum Fuse Amperes (A)
MSC :
Maximum Starting Current (A)
RLA :
Rated Load Amperes (A)
OFM :
Outdoor Fan Motor
kW :
Fan Motor rated output (kW)
FLA :
Full Load Amperes (A)
Содержание MULTI V WATER IV ARWN080LAS4
Страница 1: ...Heat Pump 380 415V 380V R410A 50Hz 60Hz 0CVW0 01N Replaces 0CVT0 01M P No MFL61741615 ...
Страница 27: ...17 MULTI V Water IV Heat Pump Outside Units 4 Wiring Diagrams ARWN080LAS4 ARWN100LAS4 ARWN140LAS4 ...
Страница 28: ...MULTI V Water IV Heat Pump 4 Wiring Diagrams 18 Outside Units ARWN200LAS4 ...
Страница 392: ...Special Guide MULTI V Water IV Heat Pump 1 Cautions for Refrigerant Leaks ...