44
MULTI V Water IV
Heat Pump
Installation of Outside Units
10. Cooling tower applied method
CAUTION
When the open type cooling tower is used and the water supply is directly connected to the 2nd heat exchanger,
product damage by alien particle cannot be repaired for free.
• Always use the 2nd heat exchanger.
[Open type cooling tower + Middle heat exchanger]
[Closed type cooling tower]
Heat exchanger is installed between the cooling tower
and outside unit system piping, and the temperature
difference between 1st side and 2nd side is maintained
constantly
Heat source water of the cooling tower is supplied
directly to the outside unit system.
Open type
cooling tower
1
st
side
2
nd
side
Heat exchange
Closed type
cooling tower