5. Field Wiring
21
MULTI V Water IV
Heat Pump
Outside Units
WARNING
•
Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
•
Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
the power supply.
•
Install the main switch that can interrupt all the power sources in an integrated manner because this
system consists of the equipment utilizing the multiple power sources.
•
If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on
and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outside unit
The GND terminal at the main PCB is a ‘-’ terminal for dry contact. It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A, B-B)
̰
Example Connection of Communication Cable
[BUS type]
• Connection of communication cable must be installed
like below figure between indoor unit to outside unit.
[STAR type]
• Abnormal operation can be caused by communication
defect, when connection of communication cable is
installed like below figure(STAR type).
3
4
3
4
3
4
Slave1
Outdoor Unit
Master
Outdoor unit
Slave2
Outdoor Unit
Master
Outdoor Unit
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
Содержание MULTI V WATER IV ARWN080LAS4
Страница 1: ...Heat Pump 380 415V 380V R410A 50Hz 60Hz 0CVW0 01N Replaces 0CVT0 01M P No MFL61741615 ...
Страница 27: ...17 MULTI V Water IV Heat Pump Outside Units 4 Wiring Diagrams ARWN080LAS4 ARWN100LAS4 ARWN140LAS4 ...
Страница 28: ...MULTI V Water IV Heat Pump 4 Wiring Diagrams 18 Outside Units ARWN200LAS4 ...
Страница 392: ...Special Guide MULTI V Water IV Heat Pump 1 Cautions for Refrigerant Leaks ...