MULTI V Water IV
Heat Pump
7. Capacity tables
316
Outside Units
Note
1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under
standard conditions. (Moreover, under partial load conditions there is only a minor deviation from the rate of
change in capacity shown in the above figures.)
2. With this outside unit, evaporating pressure constant control when cooling, and condensing pressure constant
control when heating is carried out.
3. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease
4. Method of calculating cooling / heating capacity : maximum cooling / heating capacity of outside units
= cooling / heating capacity of outside units obtained from capacity table X capacity correction factor due to
piping length to the farthest indoor unit
5. Equivalent piping length for Y branch and other pipes can be calculated with following table.
6. When the any one (or both) of below conditions are satisfied, the diameter of main pipe must be increased.
• The equivalent length between outdoor unit and the farthest indoor unit is 90m or more (Liquid and Gas pipes
are increased)
Refer to the table (Refrigerant pipe diameter from outdoor unit to first branch.) in the 'installation of outside
units' part.
7. Read cooling / heating capacity rate of change in the above figures based on the following equivalent length. :
overall equivalent length = (equivalent length of main pipe) X correction (equivalent length after first
branching)
•
8, 10, 14, 16, 18, 20, 22, 24, 28, 30, 34HP
•
40, 42, 44, 48, 50, 54, 60HP
•
62, 64, 68, 70, 74, 80HP
mm
(inch)
Ø6.35 Ø9.52 Ø12.7 Ø15.88 Ø19.05 Ø22.2 Ø25.4 Ø28.58
Ø31.8
Ø34.9
Ø38.1
Ø41.3
Ø44.5
Ø53.98
(1/4)
(3/8)
(1/2)
(5/8)
(3/4)
(7/8)
(1)
(1-1/8)
(1-1/4)
(1-3/8)
(1-1/2)
(1-5/8)
(1-3/4)
(2-1/8)
Elbow
m(inch)
0.16
(6.3)
0.18
(7.1)
0.2
(7.9)
0.25
(9.8)
0.35
(13.8)
0.4
(15.7)
0.45
(17.7)
0.5
(19.7)
0.55
(21.7)
0.6
(23.6)
0.65
(25.6)
0.7
(27.6)
0.75
(29.5)
0.85
(33.5)
Y
Branch
m(inch)
0.5(19.7)
Header
m(inch)
1(39.4)
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1.0
0.5
Heating(Liquid pipe)
1.0
0.2
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1.0
0.5
Heating(Liquid pipe)
1.0
0.4
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1.0
-
Heating(Liquid pipe)
1.0
0.4
Содержание MULTI V WATER IV ARWN080LAS4
Страница 1: ...Heat Pump 380 415V 380V R410A 50Hz 60Hz 0CVW0 01N Replaces 0CVT0 01M P No MFL61741615 ...
Страница 27: ...17 MULTI V Water IV Heat Pump Outside Units 4 Wiring Diagrams ARWN080LAS4 ARWN100LAS4 ARWN140LAS4 ...
Страница 28: ...MULTI V Water IV Heat Pump 4 Wiring Diagrams 18 Outside Units ARWN200LAS4 ...
Страница 392: ...Special Guide MULTI V Water IV Heat Pump 1 Cautions for Refrigerant Leaks ...