34
MULTI V Water IV
Heat Pump
Installation of Outside Units
9. Electrical Wiring
9.1 Areas of Caution
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations and guidance of each electric power company.
WARNING
Be sure to have authorized Electrical engineers do electric work using special circuits in accordance with
regulations and this installation manual. If power supply circuit has a lack of capacity or electric work
deficiency, it may cause an electric shock or fire.
2. Install the outside unit transmission line away from the power source wiring so that it may not affected by electric
noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to outside unit.
CAUTION
Be sure to correct the outside unit to earth. Do not connect earth line to any gas pipe, water pipe,
lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
4. Give some allowance to wiring for electrical part box of indoor and outside units, because the box is sometimes
removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will be
burnt out.
6. Use 2-core shield cable for transmission line.( mark in the figure below) If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor transmission and receiving will cause
erroneous operations. ( mark in the figure below)
7. Only the transmission line specified should be connected to the terminal block for outside unit transmission.
2-core shield cable
Multi-core cable
Remote
control
Remote
control
Remote
control
Remote
control
Indoor
Unit
Outside Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Outside Unit
Outside Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Содержание MULTI V WATER IV ARWN080LAS4
Страница 1: ...Heat Pump 380 415V 380V R410A 50Hz 60Hz 0CVW0 01N Replaces 0CVT0 01M P No MFL61741615 ...
Страница 27: ...17 MULTI V Water IV Heat Pump Outside Units 4 Wiring Diagrams ARWN080LAS4 ARWN100LAS4 ARWN140LAS4 ...
Страница 28: ...MULTI V Water IV Heat Pump 4 Wiring Diagrams 18 Outside Units ARWN200LAS4 ...
Страница 392: ...Special Guide MULTI V Water IV Heat Pump 1 Cautions for Refrigerant Leaks ...