9. Electrical Wiring
37
MULTI V Water IV
Heat Pump
Installation of Outside Units
9.3 Transmission and Power Lines
1.
Transmission cable
• Types : shielding wire CVVS or CPEVS
• Use wires of size : 1.0 ~ 1.5 mm
2
• Insulation material : PVC
• Maximum allowable temperature: 60°C
• Maximum allowable line length: under 300m
2.
Remote control cable
• Types : 3-core cable
3.
Simple central control cable
• Types : 4-core cable (Shielding wire)
• Use wires of size : 1.0 ~ 1.5 mm
2
• Insulation material : PVC
4.
Separation of transmission and power lines
• If transmission and power lines are run alongside each other then here is a strong likelihood of operational
faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic
coupling.
Note
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m the figures
will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the table should
be increased.
• If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits.
• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
conduit.
• In the same way, when grouping the power lines and signal lines should not be bunched together.
CAUTION
• If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the apparatus
must be carried out by a qualified person.
• Use a power wire pipe for the power wiring.
Current capacity of power line
Spacing
100V or more
10A
300mm
50A
500mm
100A
1,000mm
Exceed 100A
1,500mm
Содержание MULTI V WATER IV ARWN080LAS4
Страница 1: ...Heat Pump 380 415V 380V R410A 50Hz 60Hz 0CVW0 01N Replaces 0CVT0 01M P No MFL61741615 ...
Страница 27: ...17 MULTI V Water IV Heat Pump Outside Units 4 Wiring Diagrams ARWN080LAS4 ARWN100LAS4 ARWN140LAS4 ...
Страница 28: ...MULTI V Water IV Heat Pump 4 Wiring Diagrams 18 Outside Units ARWN200LAS4 ...
Страница 392: ...Special Guide MULTI V Water IV Heat Pump 1 Cautions for Refrigerant Leaks ...