8. Refrigerant Piping System
29
MULTI V Water IV
Heat Pump
Installation of Outside Units
– Apply Oil Trap as shown below when the length of the pipe between the outside units is more than 2m.
Otherwise, the unit may not operate properly.
– When connecting the pipes between the outside units, the accumulation of oil in the slave outside unit should
be avoided. Otherwise, the unit may not operate properly.
(Example 3)
(Example 1)
(Example 2)
(Example 1)
Toward indoor unit
Toward indoor unit
Toward indoor unit
2m
Toward indoor unit
2m
2m
0.2m
Oil Trap
Toward indoor unit
Toward indoor unit