Installation Manual
41
Refrigerant piping installation
➲
Total piping length = A+B+C+a+b+c+d+e
≤
220m
Longest piping length
Equivalent piping length
A+B+b
≤
120m
A+B+b
≤
140m
Longest piping length after 1st branch
B+b
≤
30m
Difference in height(Outdoor Unit
↔
Indoor)
H
≤
50m (40m : Outdoor Unit is lower than Indoor Units)**
Difference in height (Indoor Unit
↔
Indoor Unit)
h
≤
15m
*L
l
H
h
*: Must be satisfied both conditions
Caution
: ***:Indoor Unit should be installed at lower position than the header.
WARNING
Piping length after header branching (a~f)
It is recommended that difference of the piping length connected to the Indoor Unit is minimized.
Performance difference between Indoor Units may occur.
**: Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose.
• Piping length from outdoor branch to outdoor unit
≤
10m, equivalent lengh : max 13m
(for 16HP or more)