36
Outdoor Unit
Refrigerant piping installation
Longest piping length
**Equivalent piping length
A+f
≤
120m
A+f
≤
140m
Longest piping length after 1st branch
f
≤
30m
Difference in height(Outdoor Unit
↔
Indoor Unit)
H
≤
50m (40m : Outdoor Unit is lower)***
Difference in height (Indoor Unit
↔
Indoor Unit)
h
≤
15m
*L
l
H
h
*: Must be satisfied both conditions
Caution
: ***:Indoor Unit should be installed at lower position than
the header.
➲
Total piping length = A+a+b+c+d+e+f
≤
220m
WARNING
Piping length after header branch-
ing (a~f)
It is recommended that difference
of the piping length connected to
the Indoor Unit is minimized.
Performance difference between
Indoor Units may occur.
10m or
less
Branch pipe can not be used after
header
2 Outdoor Units
Example : 6 Indoor Units connected
: Outdoor Unit
: Header branch
: Indoor Units
: Sealing
: Connection branch pipe
between Outdoor units:
ARBL202C
➲
Sub Outdoor Unit ~ Connection branch pipe
Pipe diameter (E)
High/Low Pressure Common pipe
(mm)
Ø19.05(3/4 inch)
Ø12.7(1/2 inch)
Ø28.58(1
1
/
8
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
➲
Connection branch pipe
~ Main pipe diameter (A)
Ø19.05(3/4 inch)
Ø38.1(1
1
/
2
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
**: Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose.
• Piping length from outdoor branch to outdoor unit
≤
10m, equivalent lengh : max 13m
(for 16HP or more)