60
Outdoor Unit
Electrical Wiring
◆
Example Connection of Transmission Cable
3 Outdoor Units
Power supply switch
(Switch fuse)
3 Phase Power line
Transmission line (3 line): Wired remote control
Single Phase of power supply line
Transmission line (2 shield line):
Between Outdoor Unit and Outdoor Unit
Pull Box
Main Power supply Line
Branch Line
Main
Sub1
Sub2
Transmission line (2 shield line):
Between Indoor Unit and Outdoor Unit
*Power supply
*Power supply
Between Indoor and Main Outdoor unit
Between Main Outdoor and Sub Outdoor unit
Indoor
Unit
Outdoor
Unit
Central
Controller
Indoor
Unit
Outdoor
Unit
Outdoor
Unit
Central
Controller
Main
Outdoor Unit
Main
Outdoor
Unit
Sub 1
Outdoor
Unit
Outdoor
Unit
Sub 2
Outdoor
Unit
The GND terminal is a '–' terminal for the central controller, not Ground Line
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
*Power supply
Model Name
Outdoor
Indoor
LRU * * * * 8T1
50Hz, 380 ~ 415V
50Hz, 220 ~240V
3 Phase 4 wire power line
Single phase power line
LRU * * * * 9T1
60Hz, 380V
60Hz, 220V
3 Phase 4 wire power line
Single phase power line
LRU * * * * BT1
60Hz, 220V
60Hz, 220V
3 Phase 3 wire power line
Single phase power line