54
Outdoor Unit
Control box and connecting position of wiring
- Remove all of the screws on front panel by pulling it forward.
- Connect Main Outdoor Unit with Sub Outdoor Units,
and Main Outdoor with Indoor Units through the ter-
minal block for transmission lines.
- When making an indoor/outdoor connection with
shielded wiring, connect the shield ground to the
earth screw. When making a central control system
connection with shielded wiring, use the terminal
block for central control.
WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
Noise Filter
Magnetic contactor
Main PCB
Magnetic contactor
Sub PCB
Fuse
Reactor
(Inverter Comp.)
Interter
Board
Capacitor
Cover
Heatsink
(Inverter Comp
Driver)
Control board for inverter fan
Transformer
Transformer
Connect the ground line of
distribution panel here.
Capacitor
Ground Terminal
for Transmission
Line Shield
Take care of the phase sequence of
3-phase 4-wire power system.
Main unit
Sub unit
Front Panel
Electrical Wiring