Installation Manual
37
Refrigerant piping installation
Branch pipe can not be used after header
Example : 6 Indoor Units connected
: Outdoor Unit
: Header branch
: Indoor Units
: Sealing
: Connection branch pipe
between Outdoor units:
ARBL302C
: Connection branch pipe
between Outdoor units:
ARBL202C
10m or
less
3 Outdoor Units
Longest pipeinglength
**Equivalent piping length
A+f
≤
120m
A+f
≤
140m
Longest piping length after 1st branch
f
≤
30m
Difference in height(Outdoor Unit
↔
Indoor Unit)
H
≤
50m (40m : Outdoor Unit is lower)***
Difference in height (Indoor Unit
↔
Indoor Unit)
h
≤
15m
*L
l
H
h
*: Must be satisfied both conditions
Caution
: ***:Indoor Unit should be installed at lower position than the header.
➲
Sub2 Outdoor unit ~ Connection branch pipe
Pipe diameter (F)
High/Low Pressure Common pipe
(mm)
Ø19.05(3/4 inch)
Ø12.7(1/2 inch)
Ø28.58(1
1
/
8
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
High/Low Pressure Common pipe
(mm)
Ø19.05(3/4 inch)
Ø19.05(3/4 inch)
Ø38.1(1
1
/
2
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
➲
Connection branch pipe
~ Connection branch pipe
Pipe diameter (E)
➲
Connection branch pipe
~ Main pipe diameter (A)
➲
Total piping length = A+a+b+c+d+e+f
≤
220m
Ø22.2(7/8 inch)
Ø44.5(1
3
/
4
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
WARNING
Piping length after header branch-
ing (a~f)
It is recommended that difference
of the piping length connected to
the Indoor Unit is minimized.
Performance difference between
Indoor Units may occur.
**: Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose.
• Piping length from outdoor branch to outdoor unit
≤
10m, equivalent lengh : max 13m
(for 16HP or more)