Installation Manual
35
Refrigerant piping installation
◆
Header Method
Longest piping length
**Equivalent piping length
A+f
≤
120m
A+f
≤
140m
Longest pipeing length after 1st branch
f
≤
30m
Difference in height(Outdoor Unit
↔
Indoor Unit)
H
≤
50m ( 40m : Outdoor Unit is lower)***
Difference in height (Indoor Unit
↔
Indoor Unit)
h
≤
15m
*L
l
H
h
1 Outdoor Unit(Half size)
Example : 6 Indoor Units connected
: Outdoor Unit
: 1st branch
: Indoor Units
: Sealing
➲
Main pipe diameter (A)
➲
Total piping length = A+a+b+c+d+e+f
≤
220m
H 50m
L 120m
15m
Branch pipe can not be used after header
*: Must be satisfied both conditions
Caution
: ***:Indoor Unit should be installed at lower position than the header.
**: Assume equivalent pipe length of
Y branch to be 0.5m, that of head-
er to be 1m, calculation purpose.
Liguid pipe
Ø9.52(3/8 inch)
Gas pipe
Ø19.05(3/4 inch)
-
Liguid pipe
Ø9.52(3/8 inch)
Gas pipe
Ø22.2(7/8 inch)
Liguid pipe
Ø12.7(1/2 inch)
Gas pipe
Ø28.58(1
1
/
8
inch)
PIPE
1 Outdoor Unit
(Half Size)
1 Outdoor Unit
(Full Size)
5HP
6HP
OVER
8HP