65
Pre-commissioning and Maintenance
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Figure 66: Indoor Unit Auto Addressing Procedure Flowchart.
Auto addressing procedure is complete. The number of indoor
units that have successfully completed the auto addressing
procedure will display on the LED for ten (10) seconds.
Address number of each indoor unit is shown on the wired remote controller
display or on the indoor unit display. The address number will disappear
after pressing the on / off button on the remote controller. If 01, 02,... 08
is seen, that means that eight (8) indoor units have been successfully
auto addressed.
Initiate auto addressing procedure.
Wait 45 seconds.
Power On.
Press/hold the red Auto Address
Button for five (5) seconds.
LED displays = 88
Wait three (3) to seven (7) minutes.
LED displays
Auto addressing successful.
YES
NO
Check the communication
cable connections.
= 88
Outdoor unit sequences through
self diagnostics check. Wait until
LED is blank.
Indoor Unit Auto Addressing
PRE-COMMISSIONING