Water Quality Requirements
Impurities in the water can influence the performance and life expectancy of the water cooled unit. The water should be tested and treated
using a local water treatment professional. The following levels should be maintained:
Closed Type System
Effect
Circulating Water
Supplemented Water
Corrosion
1
Scale
1
Basic Item
pH (77°F)
7.0 ~ 8.0
7.0 ~ 8.0
●
●
Conductivity (77°F) mS/m
Below 30
Below 30
●
●
Chlorine ions (mg Cl
-
/ℓ)
Below 50
Below 50
●
Sulfate ions (mg SO
4
2
/ℓ)
Below 50
Below 50
●
●
Acid consumption (pH4.8) (mgCaCO
3
/ℓ)
Below 50
Below 50
●
Total Hardness (mg CaCO
3
/ℓ)
Below 70
Below 70
●
Calcium Hardness (mg CaCO
3
/ℓ)
Below 50
Below 50
●
Ionic-static silica (mg SiO
2
/ℓ)
Below 30
Below 30
●
Reference Item
Iron (mg Fe/ℓ)
Below 1.0
Below 0.3
●
●
Copper (mg Cu/ℓ)
Below 1.0
Below 0.1
●
Sulfate ion (mg SO42/ℓ)
Must not be detected
Must not be detected
●
Ammonium ion (mg NH4+)ℓ
Below 0.3
Below 0.1
●
Residual chlorine (mg Cl/ℓ)
Below 0.25
Below 0.3
●
Free carbon dioxide (mg CO2/ℓ)
Below 0.4
Below 4.0
●
Stability index
●
●
1
The “●” mark for corrosion and scale means that there is a possibility of occurrence.
• Inhibitors should be used in the water loop, especially if water temperature operates above 104°F.
• Air shall be purged from the system.
Note:
WATER CIRCUIT INSTALLATION
Piping System Specifications
Pipe Insulation
Water pipe insulation is suggested in the following conditions:
• Where water pipe is subject to freezing.
• Water pipe where water can condense on surface of pipe from ambient room temperatures higher than temperature of water in the pipe. If
water temperature is maintained at 68°F in winter and 86°F in summer, insulation will not be required.
• On boiler water pipes to save energy losses from heat source.
• On condensate drain lines.
• Where required by local code.
Table 24: Minimum Water Quality Requirements.