Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Figure 64: Water Source to Indoor Unit Communications Cable Termination Detail.
Communication Cables Between the Water Source Unit and the Indoor Units
Between Water Mini Unit and Indoor Units
IDU B
SODU B
INT B
SODU A
IDU A
INT A
TR / TQ Cassette Frames and
All Other Indoor Unit Styles
TM / TN / TP Cassette
Frames Only
1(L1) 2(L2)
3(A) 4(B)
1(L1) 2(L2) 3(L1) 4(L2)
6(B)
5(A)
DRY 1 DRY 2 GND
The terminal tagged “GND” on the water source unit main PCB is not an earth ground terminal. It is a neutral (-) terminal provided to connect
the water source unit to central control devices.
Communications Cables
ELECTRICAL SYSTEM INSTALLATION
• Field Provided 18 Gauge Stranded Two-core
Cable (Shielded)
• Insulation material as recommended by local
code.
Communication Cables Between the Water Source Unit and the Central
Control Device
• Field Provided 18 Gauge Stranded Two-core Cable (Shielded)
• Insulation material as recommended by local code.
Connect all central control devices such as AC Smart II, AC Smart Premium, ACP, BACnet and LonWorks gateways, and energy recovery
ventilators all on the same cable. Order does not matter. Polarity does. Keep “A” terminals with “A” terminals, and “B” terminals with “B”
terminals. Starting at the water source unit, terminate the cable on terminals Internet A and Internet B. Route the cable as needed between
each device.
Note:
Connect the shield to ground ONLY at the water source unit. Tie shields together at each termination point.
Note: