Device Connection Limitations
• The minimum number of connected and operating indoor units to a Multi V Water Mini system is one, taking into consideration of the mini-
mum combination ratio.
• The maximum number of indoor units on a Multi V Water Mini heat pump systems is:
One of the most critical elements of a Multi V Water Mini system is the refrigerant piping. The table below lists pipe length limits that must be
followed in the design of a Multi V Water Mini refrigerant pipe system:
Table 7: Multi V Water Mini Liquid Refrigerant Pipe Design Limitations.
Pipe Length
(ELF = Equivalent Length of pipe
in Feet)
Longest total equivalent piping length
≤475.7 feet
Longest distance from water source unit to indoor
unit
230 feet (Actual)
295.2 feet (Equivalent)
Distance between fittings and indoor units
≥20 inches
Distance between fittings and Y-branches
≥20 inches
Distance between two Y-branches
≥20 inches
Distance between Header and indoor units
≥20 inches
Minimum distance between indoor unit to any
Y-branch
3 feet from indoor unit to Y-branch
Maximum distance between first Y-branch to farthest
indoor unit
≤ 131 feet
Elevation (All Elevation
Limitations are Measured in
Actual Feet)
Water-source unit above or below indoor unit
≤ 98.4 feet
Between any two indoor units
≤ 49 feet
Table 8:
Equivalent Piping Length for Y-branches, Headers, and Typical Refrigeration Elbows.
Component
Size (Inches)
1/4
3/8
1/2
5/8
3/4
7/8
1
1-1/8
1-1/4
1-3/8
1-1/2
1-5/8
1-3/4
2-1/8
Elbow (ft.)
0.5
0.6
0.7
0.8
1.2
1.3
1.5
1.6
1.8
2.0
2.1
2.3
2.5
2.8
Y-branch (ft.)
1
1.6
Header (ft.)
3.3
1
Kit contains two Y-branches: one for liquid and one for vapor.
ARWN038GA2 = 6
ARWN048GA2 = 8
ARWN053GA2 = 9
REFRIGERANT PIPING DESIGN
System Engineering