Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Variable Water Flow Control Kit DIP Switch Settings
Using ‘SWDIP’, select the control function using the DIP switches as described below.
• After the DIP switch is changed, the reset switch must be pressed to reflect the setting.
• Before operating the water source unit, check the water flow rate and the PCB voltage signal.
• Minimum flow rate recommended 40% of rated flow rate; if the flow rate is lower, it will damage the water source unit.
ON
L1 2 3 4
OFF
Default is L1: ON, L2: OFF.
Table 25: Output Signal Setting.
DIP Switch Setting
Function
Control signal : DC 0V(OFF), DC 8~10V(ON)
Control signal : DC 0V(OFF), DC 6~10V(ON)
Control signal : DC 0V(OFF), DC 4~10V(ON)
Default status
Control signal : DC 0V(OFF), DC 2~10V(ON)
DIP Switch Setting
Function
RS-485 communication function enable
RS-485 communication function disable
ON
L1 2 3 4
ON
L1 2 3 4
OFF
OFF
ON
L1 2 3 4
ON
L1 2 3 4
ON
L1 2 3 4
ON
L1 2 3 4
OFF
OFF
OFF
OFF
Figure 57: DIP Switch Setting.
Table 26: RS-485 Communication Function Setting.
WATER CIRCUIT INSTALLATION
Variable Water Flow Control Kit
Note: