Wiring and Water Piping for Unit
Installation Manual
43
ENGLISH
Water condensation on the floor
While cooling operation, it is very important to keep leaving water temperature higher than 16 ℃.
Otherwise, dew condensation can be occurred on the floor.
If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator
While cooling operation, cold water may not flow to the radiator. If cold water enters to the radiator,
dew generation on the surface of the radiator can be occurred.
Drainage treatment
While cooling operation, condensed dew can drop down to the bottom of the unit. In this case,
prepare drainage treatment (for example, vessel to contain condensed dew) to avoid water drop.