MODBUS PROTOCOL REGISTERS
Discrete Register
Register Address
Meaning
10001
Reserve
10002
0 : Load Water Flow Switch Off
1 : Load Water Flow Switch On
10003
Reserve
10004
0 : Load Water Pump Output Off
1 : Load Water Pump Output On
10005
Reserve
10006
0 : Load Water Pump Interlock Off
1 : Load Water Pump Interlock On
10007~10104
Reserve
10105
0 : Cycle 1's 4 Way Valve 1 Off
1 : Cycle 1's 4 Way Valve 1 On
10106
0 : Cycle 1's 4 Way Valve 2 Off
1 : Cycle 1's 4 Way Valve 2 On
10107
0 : Cycle 1's Hot gas1 Off
1 : Cycle 1's Hot gas1 On
10108
0 : Cycle 1's Hot gas2 Off
1 : Cycle 1's Hot gas2 On
10109
0 : Cycle 1's Sump Heater 1 Off
1 : Cycle 1's Sump Heater 1 On
10110
0 : Cycle 1's Sump Heater 2 Off
1 : Cycle 1's Sump Heater 2 On
10111~10118
Reserve
10119
0 : Cycle 1's Inverter Compressor 1 Off
1 : Cycle 1's Inverter Compressor 1 On
10120
0 : Cycle 1's Inverter Compressor 2 Off
1 : Cycle 1's Inverter Compressor 2 On
10121~10208
Reserve