128
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
LG
Air-Cooled Heat Pump Inverter Scroll Chiller Installation and Owners Manual
ERROR CODE TABLES
CHxx180
Plate type heat exchanger frozen
When the load outlet water temperature is maintained at 3 °C or below after
the compressor started or if the low pressure is maintained at less than 660
kPA after the compressor started
Stop applicable cycle
Automatically return to normal condition
CHxx193
Surge in fan board heat emitting plate temperature
Surge in fan board heat sink temperature
Stop applicable cycle
Automatically return to nomal condition
CHxx194
Fan board heat emitting plate temperature sensor error
Fan board heat emitting plate temperature sensor is short/open
Stop applicable cycle
Automatically return to nomal condition
Error code
Error name
Error condition
Control during error
Cancel condition
CHxx145
Main Board - External Board communication Error
Main Board - External Board communication Error
Stop applicable cycle
Automatically return to normal condition
CHxx150
Liquid Compression Prevention Error
Liquid Compression Prevention Error
Stop applicable cycle
Automatically return to normal condition
CHxx151
Reversing valve switching failed
Mode switching failed
Stop applicable cycle
Automatically return to nomal condition