Air-Cooled Heat Pump Inverter Scroll Chiller Installation and Owners Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
REFRIGERANT PIPING AND SENSOR DIAGRAM /
OPERATION RANGE AND LIMIT
1. Proper Glycol Solution is required for LWT at
or below 32°F.
2. Proper Glycol Solution is required for Ambient
Operation at or below 41°F
3. Operation Limit Recommendation for 208-230V
is 120°F.
4. LG LATS ISC Selection Software is to be used to
confirm selection and performance.
68°F LWT (100% to 65%)
44°F LWT (100% to 50%)
14°F LWT (77% to 33%)
45
35
25
105
95
85
75
65
125
Ambient Air Degrees F
45
55
65
75
85
95
25
35
EW
T
a
nd
L
W
T
C
hi
lle
d
W
at
er
T
em
pe
ra
tu
re
D
eg
re
es
F
ACHH Chilled Water Operation Limits and Performance
Cold Water Inlet
Temperature F
Cold Water Outlet
Temperature F
Ambient Range
O
pe
ra
tio
n
R
an
ge
18°F to 88°F
14°F to 68°F
5°F to 125°F
105
115
15
5
5
15
55
Approved
Δ betw
een EWT and LWT is 4°F to 20°F
5
15
25
35
45
55
50%
30%
Ambient Air Degrees F
40%
Cooling Capacity Performance 10
°Δ
T (EWT to LWT)
100%
90%
80%
70%
60%
75
85
95
105
115
125
65