MODBUS PROTOCOL REGISTERS
Register Address
Meaning
30249~30300
Reserve
30301, 30302
Cycle 3's Load Water Output Temperature
30303, 30304
Cycle 3's Load Water Input Temperature
30305~30308
Reserve
30309
Cycle 3's Condensation Temperature (Left)
30310
Cycle 3's Condensation Temperature (Right)
30311
Cycle 3's Evaporation Temperature (Left)
30312
Cycle 3's Evaporation Temperature (Right)
30313
Inverter Compressor 1's Frequency of Cycle 3
30314
Inverter Compressor 2's Frequency of Cycle 3
30315
Cycle 3's High Pressure (Left)
30316
Cycle 3's High Pressure (Right)
30317
Cycle 3's Low Pressure (Left)
30318
Cycle 3's Low Pressure (Right)
30319
Cycle 3's Operation Current (Left)
30320
Cycle 3's Operation Current (Right)
30321
Main EEV's Status Value of Cycle 3 (Left)
30322
Main EEV's Status Value of Cycle 3 (Right)
30323~30324
Reserve
30325
Discharge Temperature of Cycle 3's Inverter Compressor1
30326
Discharge Temperature of Cycle 3's Inverter Compressor2
30327
Intake Temperature of Cycle 3's Inverter Compressor1
30328
Intake Temperature of Cycle 3's Inverter Compressor2
30329
Cycle 3's Liquid Pipe Temperature (Left)
30330
Cycle 3's Liquid Pipe Temperature (Right)
30331
Cycle 3's Hex Temperature (Left)
30332
Cycle 3's Hex Temperature (Right)
30333~30344
Reserve
30345
Accumulated Operation Time of Cycle 3's Inverter Compressor 1
(Upper Level)
30346
Accumulated Operation Time of Cycle 3's Inverter Compressor 1
(Lower Level)
30347
Accumulated Operation Time of Cycle 3's Inverter Compressor 2
(Upper Level)
30348
Accumulated Operation Time of Cycle 3's Inverter Compressor 2
(Lower Level)
30349~39997
Reserve
39998
Product Group Info.
39999
Product Type Info.