130
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
LG
Air-Cooled Heat Pump Inverter Scroll Chiller Installation and Owners Manual
2. Hot Water Set Point (2 ~ 10 V, 4 ~ 20 mA)
: UI3 (Mode Heat)
Volt [V]
500
Ω
[mA]
Heat Set Point
(30 ~ 70) [°C]
Heat Set Point
(86 ~ 158) [°F]
Etc
0.0
0.0
No Control
(Disconnected)
No Control
(Disconnected)
0.2
0.4
0.4
0.8
0.6
1.2
0.8
1.6
1.0
2.0
1.2
2.4
1.4
2.8
1.6
3.2
1.8
3.6
2.0
4.0
30
86
2.2
4.4
31
87.8
2.4
4.8
32
89.6
2.6
5.2
33
91.4
2.8
5.6
34
93.2
3.0
6.0
35
95
3.2
6.4
36
96.8
3.4
6.8
37
98.6
3.6
7.2
38
100.4
3.8
7.6
39
102.2
4.0
8.0
40
104
4.2
8.4
41
105.8
4.4
8.8
42
107.6
4.6
9.2
43
109.4
4.8
9.6
44
111.2
5.0
10.0
45
113
5.2
10.4
46
114.8
5.4
10.8
47
116.6
5.6
11.2
48
118.4
5.8
11.6
49
120.2
6.0
12.0
50
122
6.2
12.4
51
123.8
6.4
12.8
52
125.6
6.6
13.2
53
127.4
6.8
13.6
54
129.2
7.0
14.0
55
131
REMOTE DESIRED TEMPERATURE CONTACT
POINTS