28
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
LG
Air-Cooled Heat Pump Inverter Scroll Chiller Installation and Owners’
Manual
Oceanside Installation Precautions
•
Avoid installing the chiller where it would be directly exposed to ocean winds.
• Install the chiller on the side of the building opposite from direct ocean winds (so the building can block the winds).
• Select a location with good drainage.
If the chiller is installed in an area where it would be directly exposed to ocean winds, additional anti-corrosion treatment will need to be applied to
the chiller condenser. Ocean winds will cause corrosion, particularly on the condenser, which, in turn could cause product malfunction or inefficient
performance.
If the chiller must be placed in a location where it
would be subjected to direct ocean winds, install
a concrete (or similar material) windbreaker. The
windbreaker wall height and width must be at least
one and a half (1-1/2) times wider than the chiller,
and must provide at least 40 inches clearance to
allow for airflow.
Ocean Winds
Wall
Ocean Winds
Ocean Winds
PLACEMENT CONSIDERATIONS